Shunt Trip Testing Update!
In our previous post from Fall of 2024, I stated:
1. The initiating devices (heat detectors) and shunt-trip will need to be tested. Generally, this is done during your annual building confidence testing.
- A fire/life safety contractor will test the heat and smoke detectors. 
- A Class 1 electrician is needed to test the shunt-trip. 
The second bullet point is incorrect. It should be changed to state:
The initiating devices (heat detectors) and shunt-trip will need to be tested. Generally, this is done during your annual building confidence testing. To perform the test, you will need a fire/life safety contractor to perform the following tasks:
- Shunt the disconnect using the low voltage leg. This is to test that the shunt is operating properly, i.e., the Fire Alarm Initiating Devices (FAID) sends a signal to the fire panel and removes power from the elevator. 
- Resets the “high voltage” disconnect after it has been shunted. This re-energizes the elevator and returns it to normal operation. In the case of elevators, most high voltage falls between 200V and 480V. 
- Please note… This only applies when the shunt is tripped by the fire panel. 
- However, if the shunt is tripped by high voltage, then an 01 electrician is needed. NOTE: This is not a common building application. 
To read our original post about what a shunt trip test is, please click here.
If you still have questions, please feel free to contact Sean.

